Hospital Units - H Series
Chilled Water

Cooling capacity: 32,3 to 141,0kW.

Air flow: from 2.500 to 11.200m3/h.


Hospital units - OHU

· Water heating coil with two or three-way modulating adjustment valve 

· Modulating electric heating coil (accessory)

· Post-heating water coil with two or three-way modulating valve

· Modulating electric post-heating coil (accessory)

· Autonomous modulating humidifier with immersed electrodes

· Modulating steam distributor deriving from the network (accessory)

· Heat recovery system



DOWNLOAD THE BROCHURE

1. UNITS WITH HEAT RECOVERY

2. UNITS WITHOUT HEAT RECOVERY*

* Only for extra European markets/not compatible with ERP2018

 


Unidirectional air filtering ceiling



 

Complete electrical board


The electrical board is equipped with a door-locking main switch and necessary components for protection and normal operation of the unit.

Terminals are provided for remote connection of a cumulative alarm signal and remote control of start/stop functions.


Night stand-by


When the room in not in use the flow of fresh air can be reduced to predefined set limits, maintaining the area in overpressure, and increasing the interval for the control of temperature and humidity. The room is thus kept sterile without wasting energy.

Antifreeze system


This system guarantees active protection from the risk of freezing thanks to the presence of a relative temperature sensor, installed downstream of the pre-heating coil and upstream of the cooling coil.

If the antifreeze sensor detects a temperature below that of a pre-set value, it activates emergency intervention by operating the heating at 100%.

If after a set amount of time the temperature is still under the pre-set value, the fresh air damper is closed, and fans are switched off. The anomaly is displayed on the main mask of the microprocessor as an alarm state.


Double fan


The machine can be fitted with double fan for supply, suction, and exhaust (accessory).

This ensures the machine can continue to run in complete safety, even in the event of a fan failure.

The EC FAN fans are controlled directly by the microprocessor, based on internal measurement of airflow within the unit.


 


Technical equipment

 



Hospital Units - H Series


The new generation of H Series air conditioners is optimised for operating theatres and hospitals, where the primary objective is high air quality. The H Series units, in their standard configuration, are complete with all key components (heat recovery system, cooling, pre- and

post-heating, humidification and dehumidification), sized for the treatment of full fresh air or with partial recirculation.

A flexible configuration and a high number of accessories assure the use of H Series units in applications such as: operating theatres, laboratories, clean rooms, image diagnosis rooms, wards, and intensive care units.


 

The primary objective is high air quality